ADDENDUM FOR iMXDa/iEXDa INTEGRATED EXIT DELAY SYSTEM
iMXDaCH – City of Chicago Operational Information
This addendum is a decisive supplemental to the iMXDa/iEXDa Installation and Operating Instructions (P/N
500-22175) and iMXDa/iEXDa Quick Start Guide (P/N 500-22310) which addresses the operating
notifications specifically related to compliance with the City of Chicago and related Municipal Codes.
For compliance with Section 13-160-269(a)(7) of the Municipal Code:
The Securitron – Model iMXDaCH Integrated Movement Exit Delay System will contain no selectable
operating modes for the logic timers or specialized alarm reminder operations.
The timing system is fixed with a 1 second initiating time (nuisance timed alarm) plus a 14-second
(irrevocable timed alarm) sequence and delayed lock release and egress implementation.
Automatic re-locking only occurs if the door opens and returns to the closed position and then
remains closed for a full 30 second period thereafter.
For compliance with Section 13-160-269(a)(1) of the Municipal Code:
The Securitron – Model iMXDaCH Integrated Movement Exit Delay System must be used with a UL
listed fire alarm system.
The fire alarm system must contain latching type dry contacts designated for “auxiliary” operations.
The contacts must activate for both the alarm and troubled conditions.
For compliance with Section 13-160-269(a) of the Municipal Code:
The Securitron – Model iMXDaCH Integrated Movement Exit Delay System must be used with a
Securitron ~ Model BPS-CH Series Power Supply.
The power supply unit is to be supplied without provisions for battery back-up.
Door Travel Limitations and/or Restrictions:
The Securitron – Model iMXDaCH Integrated Exit Movement Delay System must be configured to
trigger the egress initiating within one-eighth inch (1/8”) of door movement.
The maximum door travel is limited to a one-half inch (1/2”) movement measured at the strike
armature/sex bolt mounting location.
WIRING DIAGRAM FOR iMXDaCH